Permit: T05CM03758

Parcel: 140441160


Addresses:

6098 E FARMSTEAD DR

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
10/28/2005 BUILDING PRE-SLAB Approved IVRS - Inspection :*
10/26/2005 BUILDING PRE-SLAB Not ready for Inspection
10/24/2005 BUILDING PRE-SLAB Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPERTY PINS ON ALL 4 CORNERS OF LOT
2) YOU MUST REQUEST THROUGH THE COMPUTER ALL REQUIRED INSPECTIONS. YOU MUST REQUEST A ROUGH PLUMBING INSPECTION FIRST THEN AN EXCAVATED, LAYOUT PRE-SLAB AND UFER INSPECTION
3) YOU MUST PROVIDE A 10 FOOT DRAIN WASTE AND VENT WATER TEST
4) EXPOSE ALL PLUMBING UNDER SLAB
5) INSTALL ALL UNDERSLAB "P" TRAPS
6) SEVERAL LEAKS ON ROUGH PLUMBING
7) REINFORCING STEEL MUST BE 3" FRO SOIL
8) PLUMBING IS FROM FLAT TO REVERSE PITCH MUST HAVE 1/4" PER FOOT PITCH
9) HPHD22 HOLDOWNS NOT INSTALLED
10) MARK LOCATIONS OF ANCHOR BOLTS FOR BRACED WALL PANELS
11) PROVIDE FOOTERS WITH STEEL PER 2/S-1