Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 02/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAKE SURE EMERGENCY/EGRESS LIGHTING IS WORKING AND PER PLAN. 2. CORRECTLY IDENTIFY ALL BRANCH CKT'S IN PANELS INCLUDING FUTURE CKT'S 3. NEED MAIN BREAKERS IN PANEL BOARDS NEC 408.16 A,B, 4. WILL FINISH INSPECTION NEXT TRIP (1 HR) |
|
| 02/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO COVER ELECTRICAL IN BAR AREA | |
| 01/09/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 12/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFIT & HARD LIDS |
|
| 11/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK STUD WALLS EXCEPT BAR AREA | |
| 11/10/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/20/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK UNDERSLAB CONDUITS & FLOOR BOXES. | |
| 10/19/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/18/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*CHANGE CONTR. OF RECORD.CONDUIT ALREADY COVERED. |