Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM03726
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
12/12/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WRONG SIZE GUSSET PLATE ON ? 8 5" X 8" REQUIRED 2) NO HANGER EAST WALL HALF TRUSS 3) SHEARWALL NOT PER PLAN 6/DT2 KITCHEN 4) STOPPED INSPECTION, TOO MANY ITEMS MISSING FROM PREVIOUS INSPECTION |
|
12/06/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ALL RAT RUNS 2) TRUSS B-3 AT JOINT 8 WRONG SIZE GUSSET PLATE, TRUSS MEMBER IS DAMAGED 3) SHIM ALL 3 PT BEARING 4) INSIDE END TRUSS-NO HANGER NAIL TO WALL 5) HALF TRUSS ON EAST GARAGE WALL NO HANGER 6) LOOSE GUSSET ON B-4 TRUSS GARAGE 7) SHEAR TRANSFER FOR KITCHEN NOT PER PLAN 8) LEDGER ABOVE LAUNDRY ROOM NEEDS 16D COMMONS 9) MISSING HANGERS S/E BEDROOM 2ND FLOOR 10) CANNOT STRIP AT REAR GABLE 11) SOLID VERT STUDS AT BEAM SUPPORT 1ST AND 2ND FLOOR LIVING ROOM 12) #5 SHEAR TIE TO GABLE TRUSS NORTH 2ND FLOOR SHEAR TO ROOF 13) KITCHEN SHEAR WEST WALL NAIL TO ROOF 8D 6" ON CENTER 14) WALKED ROOF-ALL OK BUT KITCHEN SHEAR 15) WHAT ELEVATION IS THIS HOUSE ? |
|
11/21/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* |