Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE TO USE AN APPROVED EXTENDER RING 314.20 2. SMOKE DETECTORS TO BE ON ARC FAULT CIRCUIT 210.11 3. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 4. USE APPROVED CAR FLEX FITTING FOR WATER HEATER 5. A DISCONNECT MEANS IS NEEDED FOR WATER HEATER. 6. ROOFTOP MAINTENANCE RECEPTACLE TO BE GFCI PROTECTED. |
|
| 08/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |