Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM03718

Parcel: 134083240

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE TO USE AN APPROVED EXTENDER RING 314.20
2. SMOKE DETECTORS TO BE ON ARC FAULT CIRCUIT 210.11
3. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
4. USE APPROVED CAR FLEX FITTING FOR WATER HEATER
5. A DISCONNECT MEANS IS NEEDED FOR WATER HEATER.
6. ROOFTOP MAINTENANCE RECEPTACLE TO BE GFCI PROTECTED.
08/15/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*