Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM03717
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE. OK FOR SHEET ROCK | |
| 02/24/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ACCESS TO VOLUME CONTROL DAMPER WITH WEIGHT. ACCESS? ITEM #1 COMPLETE |
|
| 02/21/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 1 - DUCT NOT CONNECTED 2ND FLOOR ABOVE SHOWER INSULATE ALL EXPOSED SHEET METAL. RECALL FOR INSPECTION PROVIDE MIN 100 SQ.IN. MAKE UP AIR IN LAUNDRY ROOMS. NEED TO SEE SPECS. ON DRYERS. INSULATE ALL SUPPLY FITTINGS & PLENUMS WITH MIN R6 INSULATION AS PER I.E.C.C. |