Permit: T05CM03716

Parcel: 134083220

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T05CM03716

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2006 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
WATER TEST WASTE & VENT THRU ROOF OK
WATER PIPING 60 PSI TEST OK
CLOSET FLANGES OK
03/17/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO CHANGE, NO PLUMBER ON SITE
CONTRACTOR TO PAY RE-FEE
03/15/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/14/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
SPOKE WITH NEW PLUMBER ON SITE ABOUT CORRECTIONS
03/13/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPAIR DAMAGED TUB & SHOWER RISER NORTH UPSTAIRS UNIT. SEE NOTES FROM 1/13/06 INSA THIS IS NOT A COMPLETE LIST.
03/09/2006 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/07/2006 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
WATER TEST WASTE & VENT NORTH BUILDING THRU ROOF OK
1. PROVIDE SEPARATION OF HOT & COLD PIPING -
CLOSET FLANGES OK
SOUTH BUILDING:
1. LAV DRAIN AREA SHALL BE 1 1/2" NOT TO EXCEED 42"
2. DRAIN FOR SHOWER AT P-TRAP SHALL BE CORRECT.
3. SHOWER PAN BUILT ON SITE 2ND FLOOR SHALL HAVE WATER TEST AT LATER DATE.
4. SUPPORT OVERHEAD WASTE & VENT PIPING WITH APPROVED MATERIALS (PIECES OF PIPE ARE NOT)
RETEST SYSTEM
PROVIDE GAUGE WITH TEST FOR WATER PIPING OR HAVE WATER LINE PRESSURE CONNECTION.
03/03/2006 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*