Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM03715
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CLOSET FLANGES OK |
|
| 04/25/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLUMBERS TAPE IS NOT APPROVED FOR HANGING PIPE SUPPORTS. PROVIDE CORRECT APPROVED SUPPORT FOR PIPING OR FACE RE-FEE. 60 PSI TEST ON WATER PIPING OK |
|
| 04/19/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WATER TEST DWV OK 1. PROVIDE PROOF OF TEST ON ALL PIPING INCLUDING WATER PIPING. 2. PROVIDE CORRECT SUPPORT AT 4' INTERVALS ON HORIZONTAL VENT PIPING. ABOVE CEILING AND AT CHANGES OF DIRECTION. 3. PROVIDE 18" MINIMUM IN WALL COPPER PIPING AT WATER HEATER FOR MANUFACTURE. 4. NEED SEE SHOWER PAN TEST. 5. PLASTIC WATER PIPING REQUIRES SUPPORT AT 32" |
|
| 04/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ALL PIPING TO BE COMPLETE & HAVE TEST ON SYSTEMS. 2. PROVIDE CORRECT VENTING FOR HORIZONTAL VENTING BELOW FLOOD RIM OF FIXTURE. 3. TRAP ARM MAX ON 2" IS 5' THIS IS NOT A COMPLETE LIST. |