Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* - WATER TEST WASTE & VENT & WATER PIPING OK - CLOSET FLANGES OK. - NEED TO SEE TEST ON ALL SHOWER PANS ON PROJECT. |
|
| 05/08/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SECURE TUB DIVERTER, SECURE TUBING BEHIND TUB. - PROVIDE WATER TEST ON TUB OVERFLOW. - SUPPORT HORIZONTAL ABS NOT TO EXCEED 4' - USE BRASS SCREWS ON CLOSET FLANGES - NOT PLATED DECK SCREWS. - DO NOT TRIM FITTINGS - FULL HUB REQUIRED - PROVIDE 2% SLOPE MIN. - POINT OF VENT SHALL BE ABOVE FLOW LINE OF PIPE WYE OR COMBINATION FITTINGS MUST ROLL OFF AT A 45 DEGREE ANGLE TO OBTAIN. 1/6TH BENDS ALLOW PERPENDICULAR OFFSETS. IF YOU CANNOT OBTAIN UPC MIN. STANDARDS - REDESIGN. |
|
| 04/26/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WATER TEST WATER PIPING OK WASTE & VENT WATER TEST SOUTH UNIT OK 1. PROVIDE CORRECT INSTALLATION FOR HORIZONTAL VENTING BELOW FLOOD RIM OF FIXTURE IN NORTH UNIT. MAKE CORRECTION & RETEST. |