Permit: T05CM03711

Parcel: 134083170

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/12/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
- WATER TEST WASTE & VENT & WATER PIPING OK
- CLOSET FLANGES OK.
- NEED TO SEE TEST ON ALL SHOWER PANS ON PROJECT.
05/08/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/05/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE TUB DIVERTER, SECURE TUBING BEHIND TUB.
- PROVIDE WATER TEST ON TUB OVERFLOW.
- SUPPORT HORIZONTAL ABS NOT TO EXCEED 4'
- USE BRASS SCREWS ON CLOSET FLANGES - NOT PLATED DECK SCREWS.
- DO NOT TRIM FITTINGS - FULL HUB REQUIRED
- PROVIDE 2% SLOPE MIN.
- POINT OF VENT SHALL BE ABOVE FLOW LINE OF PIPE WYE OR COMBINATION FITTINGS MUST ROLL OFF AT A 45 DEGREE ANGLE TO OBTAIN. 1/6TH BENDS ALLOW PERPENDICULAR OFFSETS. IF YOU CANNOT OBTAIN UPC MIN. STANDARDS - REDESIGN.
04/26/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WATER TEST WATER PIPING OK
WASTE & VENT WATER TEST SOUTH UNIT OK
1. PROVIDE CORRECT INSTALLATION FOR HORIZONTAL VENTING BELOW FLOOD RIM OF FIXTURE IN NORTH UNIT. MAKE CORRECTION & RETEST.