Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM03709
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* SHOWER PANS OK |
|
| 07/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED TO VIEW INSTALL OF SHOWER PANS WITH TEST ON UPSTAIRS UNITS; DO NOT ROCK UNDER SIDE OF SHOWER WATER TEST WASTE & VENT, WATER PIPING, CLOSET FLANGES OK |
|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE WATER TEST THRU ROOF ON WASTE & VENT. 2. PROVIDE APPROVED COUPLINGS FOR JOINING PIPING. REMINDER: THIS IS A NEW CONSTRUCTION YOU SHOULD BE USING LIKE FOR LIKE MATERIALS. SOLVENT WELD COUPLINGS ON ABS. 3. REMINDER: CLOSET FLANGES ARE REQUIRED TO BE 1/6" ABOVE FINISH FLOOR WITH CLOSET BOND PIPE FLUSH TO TOP OF RING. BE SURE YOU PROVIDE MINIMUM 1/4" PER FOOT FALL ON ALL DRAINAGE FOR SIZES 2" + 3". |