Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM03709

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/11/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. PROTECT "SE" CABLES AT STUDS ALSO NM CABLES
2. SUPPORT NM CABLES WITHIN 12" OF BOXES & CANS & EXHAUST FANS 8' ON HORIZONTAL RUNS.
3. PROVIDE GROUND STRAP FOR 3/0 BOXES
4. MAINTAIN FIREWALL SEPARATION 300.21
5. THHN 18 NOT AN APPROVED SUPPORTING METHOD
6. ANTIOXID COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS.
7. PROTECT CONDUTOR INSIDE OF BOXES FROM SCREWS 314.43
8. PLEASE VERIFY FILL CAPACITY OF RECESSED CAN JUNTION BOX.