Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03709
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/11/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT "SE" CABLES AT STUDS ALSO NM CABLES 2. SUPPORT NM CABLES WITHIN 12" OF BOXES & CANS & EXHAUST FANS 8' ON HORIZONTAL RUNS. 3. PROVIDE GROUND STRAP FOR 3/0 BOXES 4. MAINTAIN FIREWALL SEPARATION 300.21 5. THHN 18 NOT AN APPROVED SUPPORTING METHOD 6. ANTIOXID COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS. 7. PROTECT CONDUTOR INSIDE OF BOXES FROM SCREWS 314.43 8. PLEASE VERIFY FILL CAPACITY OF RECESSED CAN JUNTION BOX. |