Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE CORRECT CONNECTION BETWEEN AIR ADMITTANCE VALVE & COMBO AT KITCHEN SINK. 2. SHALL PROVIDE CORRECT ACCESS TO BACKWATER VALVE. 3. SHALL PROVIDE SIGNAGE IN ELECTRICAL PANELS NON-METALLIC WATER PIPING NON-BONDED. 4. PROVIDE CORRECT TERMINATION OF CLEANOUTS. 5. ALL FIXTURES TO BE FUNCTIONALY & MADE WATER TIGHT. |