Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03708

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/26/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FULLY INSTALL RECEPTACLES & PLATES
2. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES AND FLUSH IN COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20
3. USE AN APPROVED CONNECTOR AT HOOD.
4. SWITCHES TO BE GROUNDED
5. USE APPROVED CORD FOR DISHWASHER -- NOT SPLICED.
6. GROUND METAL BOXES AND USE APPROVED CONNECTORS.
7. HALLWAY SWITCHES NOT WORKING CORRECT.
8. ROOF RECEPTACLES TO BE GFCI PROTECTED
9. TIGHTEN LOOSE FITTINGS
10. MAINTAIN WORKING CLEARANCES IN FRONT OF AC DISCONNECTS
11. USE APPROVED FITTINGS WITH CARFLEX
12. ANTI-ODIDE COMPOUND IS NEEDED FOR ALL ALUMINUM CONDUCTORS.