Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03708
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/26/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FULLY INSTALL RECEPTACLES & PLATES 2. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES AND FLUSH IN COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20 3. USE AN APPROVED CONNECTOR AT HOOD. 4. SWITCHES TO BE GROUNDED 5. USE APPROVED CORD FOR DISHWASHER -- NOT SPLICED. 6. GROUND METAL BOXES AND USE APPROVED CONNECTORS. 7. HALLWAY SWITCHES NOT WORKING CORRECT. 8. ROOF RECEPTACLES TO BE GFCI PROTECTED 9. TIGHTEN LOOSE FITTINGS 10. MAINTAIN WORKING CLEARANCES IN FRONT OF AC DISCONNECTS 11. USE APPROVED FITTINGS WITH CARFLEX 12. ANTI-ODIDE COMPOUND IS NEEDED FOR ALL ALUMINUM CONDUCTORS. |