Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OUTDOOR RECEPT NOT WEATHERPROOF. INSTALL EXTENSION ALSO.
2. ALL BEDROOM OUTLET TO BE AFCI PROTECTED. INCLUDES LIGHTS, FAN, SMOKES, ETC.
3. INSTALL BOX EXTENSION ON KITCHEN RECEPT IN TILE & RECEPT. UNDER SINK
4. REV POLARITY MIDDLE BEDROOM BACK UNIT
6. NEED 6' CLEARANCE TO SHELF STORAGE AREA FROM RECESSED FIXTURES.