Permit: T05CM03664

Parcel: 141018150


Addresses:

6035 S CEDAR ELM LN


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM03664

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/03/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) SEE LAST INSPECTION
10/28/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1. TRUSS PROBLEMS 1356 MODEL NEED NEW TRUSS DRAWING
2. GUSSET PLATES MISSING AT KITCHEN CIELING
3. FRONT BEARING AT 2ND FLR GAP BETWEEN PLATE & BEAM
10/26/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) NOT READY, SEE LAST INSPECTION-TRUSS PROBLEM
10/24/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSED NAILING ON ROOF
2) SHEAR PANELS (LARGE) NAIL AT 4" ON CENTER TOP 1 1/2" TO SHORT CAN'T NAIL TO ROOF
3) BLOCK ALL 3 PT BEARING TRUSSES 1ST AND 2ND FLOOR
4) GABLE TRUSSES NOT TIED TO TOP PLATES TOE NAIL AT 12" ON CENTER OR CLIP AT 48"
5) NAIL OFF ROOF
6) FRONT SHEAR CUT TO SHORT GAP BETWEEN BEAM AND PLATE
7) MORE NAILS IN VERTICAL 2 X 4 UNDER LIVING ROOM BEAM
8) MISSED WIND BRACE LAST 2ND FLOOR
9) RENAIL SHEAR EAST/SOUTH
10) CLIPS TRUSS TO TOP PLATES COMING OUT WEST 2ND FLOOR
11) NAIL FRONT PARAPET CLIPS
12) HEADER AT STAIR NOT 6'-8" MINIMUM