Permit: T05CM03661

Parcel: 12510004B


Addresses:

3421 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05CM03661

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
12/12/2006 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
05/05/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
YARD WATER LINE INTO BUILDING OK
METER NOT SET
RP NOT INSTALLED.
05/03/2006 PLUMBING - YARD WTR LINE/TEST Denied WATER SERVICE INTO BUILDING SHALL BE TYPE K
WITH BRAZED JOINTS.
PROVIDE 100 PSI TEST.
DO NOT TEST PVC WITH AIR.
02/28/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
70'-2 1/2" SCH 40 PVC BELOW GRADE W/RISERS NOT YET PRESSURE TESTED
COVER AT OWN RISK. FINAL APPROVAL UPON PRESSURE TEST