Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM03661
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* PANELS SAB, SBB CORRECTED PARALLEL RUNS TO PNLS WIRING APPROVED |
|
12/20/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/18/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/12/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY SERVICE DISCONNECT AND ALL MAINS -- NEC 230.70 B 2. BOND ALL METAL PIPING SYSTEMS - NEC 250.104 3. PROVIDE LETTER OF TORQUE FOR SERVICE 4. WIRING NOT ALLOWED THROUGH SECTIONS - NEC 408.3 A 3 5. MAKE SURE WIRING IS READY/SAFE TO BE ENERGIZED. |
|
10/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SHELL WALLS SPACE #1 NORTH, EAST, SOUTH WALLS OK INTERIOR ONLY (LIGHTING) |