Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03659

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*BOND JUNCTION BOX 250.148
SUPPORT CONDUIT WITHIN 3' OF BOX
MAINTAIN WORKING CLEARANCE AT DISCONNECT
10/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*FINISH ELECTRICAL ROOM
BOND PANEL A ENCLOSURE AND FILL UNUSED OPENINGS
AREA OCCUPIED WITHOUT FINAL OR APPROVAL PLEASE PROVIDE ACCESS TO DEVICES
BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTIBLES OR FLUSH IN COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20
USE APPROVED CONNECTORS WITH M/C, ATTACH FIXTURE AND BOX TO STRUCTURE
PLANS TO BE REVISED TO REFLECT WORK INSTALLED AND RESTAMPED
LABEL DISCONNECTS
CHECK ROOF AND DOWNSTAIRS JUNCTION BOX NEXT TIME