Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2005 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :*OBTAINED ?? ON SW GEAR TORQUING FROM CATALINA ELECTRICAL | |
| 10/17/2005 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999*LETTER OF TORQUE SW GEAR PER MANUF SPECIFICATIONS BY ELECT CONTRACTOR. PERMANENTLY ADDRESS SERVICE& FUSE EXISITING PNL LABEL DISCONNECTS IN SW GEAR. RECORD OF UFER INSPECTION. 75 KUA TRANSFORMER BOND WATER LINE # 6 DIRECTLY TO NEUTRAL OK THUR LUGS |