Permit: T05CM03642

Parcel: 125011200


Addresses:

3033 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Permit Number - T05CM03642

Inspection Description - ELECTRIC - SERVICE RELOCATION

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2005 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*OBTAINED ?? ON SW GEAR TORQUING FROM CATALINA ELECTRICAL
10/17/2005 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*LETTER OF TORQUE SW GEAR PER MANUF SPECIFICATIONS BY ELECT CONTRACTOR.
PERMANENTLY ADDRESS SERVICE& FUSE EXISITING PNL
LABEL DISCONNECTS IN SW GEAR.
RECORD OF UFER INSPECTION.
75 KUA TRANSFORMER BOND WATER LINE # 6 DIRECTLY TO NEUTRAL OK THUR LUGS