Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03642
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/27/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK ROOM 201, 213,214 | |
10/26/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* M/C CABLE TO BE SUPPORTED AS PER 300.11 AND WITHIN 12'' OF BOXES VDV CABLEING TO BE AS PER 725.2 +6, 800.2 &6 SUPPORT CABLE TRAY BOND CONDUCTOR MAINTAIN WORKING CLEARANCES FOR HVAC CONTROL PANEL CHECK POWER POLE CONNECTIONS ON FINAL AMNUFACTURERS CLIPS TO BE EFFECTIVE FOR LIGHTING IF SCREWS ARE USED 4 ON CORNERS OR 2 ON CENTER. FILL UNUSED OPENINGS-NOT FITTINGS OK TO TILE AREAS NON ESSENTIAL TO ELECTRICAL |
|
10/11/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/10/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*SUPPORT VDV CABLEING AS PER 725.6 & 800.6 M/C CABLE TO BE SUPPORTED AS PER 300.11 & 334.30 MISSING BOX COVERS & CHECK BOX FILL ATTACH FIXTURES TO GRID 410.16 |