Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03639
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2005 | ELECTRIC - ABOVE CEILING | Approved | ||
| 12/01/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK TO COVER ELECTRICAL WIRING IN CEILING. OK CORRECTIONS | |
| 11/30/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SLACK WIRES TO BE INSTALLED ON ALL FIXTURES, AT OPPOSITE CORNERS AND MADE UP TIGHT. SECURE AND SUPPORT ALL MC AND FLEX CONDUIT PROPERLY ( 12" FROM BOX'S AND EVERY 4 1/2 FEET. |
|
| 10/24/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS |