Permit: T05CM03639

Parcel: 11615190K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM03639

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2005 ELECTRIC - ABOVE CEILING Approved
12/01/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK TO COVER ELECTRICAL WIRING IN CEILING. OK CORRECTIONS
11/30/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* SLACK WIRES TO BE INSTALLED ON ALL FIXTURES, AT OPPOSITE CORNERS AND MADE UP TIGHT.
SECURE AND SUPPORT ALL MC AND FLEX CONDUIT PROPERLY ( 12" FROM BOX'S AND EVERY 4 1/2 FEET.
10/24/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK HARD LIDS