Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03631
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/18/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT M/C CABLE UP OFF OF GRID AND AS PER CODE 12" + 6' 2) EXIT SIGN TO HAVE A SUPPORT WIRE 3) FILL UNUSED OPENINGS IN BOXES-FITTING NOT ALLOWED USE SEALS 4) SECURELY ATTACH FIXTURES TO GRID-4 SCREWS ON CORNERS OR 2 ON CENTER 5) VDV CABELING TOBE AS PER 725.2 + 6, 770.2 + 6, 800.2 + 6, 800.2 + 6 6) CORRECTLY IDENTIFY CONDUCTORS AS PER CITY AMENDMENT BROWN, ORANGE, YELLOW OR BLACK, RED, BLUE |
|
07/25/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |