Permit: T05CM03631

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/24/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/18/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) SUPPORT M/C CABLE UP OFF OF GRID AND AS PER CODE 12" + 6'
2) EXIT SIGN TO HAVE A SUPPORT WIRE
3) FILL UNUSED OPENINGS IN BOXES-FITTING NOT ALLOWED USE SEALS
4) SECURELY ATTACH FIXTURES TO GRID-4 SCREWS ON CORNERS OR 2 ON CENTER
5) VDV CABELING TOBE AS PER 725.2 + 6, 770.2 + 6, 800.2 + 6, 800.2 + 6
6) CORRECTLY IDENTIFY CONDUCTORS AS PER CITY AMENDMENT BROWN, ORANGE, YELLOW OR BLACK, RED, BLUE
07/25/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*