Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/14/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCUPPER DRAINING ON SERVICE PANEL 2) GFCI IN GARAGE WON'T TRIP 3) FLEX DUCT PENETRATING GARAGE FIRE WALL 4) H20 LINE DISCONNECTED 5) H20 HTR FLUE NOT CONNECTED 6) H20 IS OFF 7) SECURE GAS LINE AT FURNACE (LEFT SIDE) 8) EXPOSE LAUNDRY CLEANOUT AT WASHER 9) NEED GFCI AT LAUNDRY SINK 10) NEED PERMANENT ADDRESS NUMBER 11) ACCESS PANEL FOR JACUZZI ON LAST SIDE DOEN'T ALLOW ACCESS TO MOTROR/CORD/PLUG 12) CLEANOUT NOT ACCESSIBLE AT KITCHEN SINK 13) SCUPPER DRAINING ON FRONT LIGHT FIXTURE |