Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/18/2006 FRAMING Approved IVRS - Inspection :*
01/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ELECTRIC AND PLUMBING NAIL PLATES
2) RUN GAS BOND
12/28/2005 FRAMING Partial Approval IVRS - Inspection :*
1) GAS TEST OK; TEST DWV, POTABLE H20 OK
2) SHIM ALL GAPS HEADERS AT BEARING POINTS
3) MAINTAIN MINIMUM 1" CLEARANCE FLUE PIPE TO COMBUSTIBLES
4) SECURE CLOTHES WASHER BOX
5) STRAP HEADERS AT BEARING
6) GAS BOND TO BE ACCESSIBLE
7) INSTALL BANG PLATES ELECTRIC HOLES WITHIN 1 1/4" STUD FACE THROUGHOUT
8) INSTALL BANG PLATES PLUMBING HOLES WITHIN 1 1/2" STUD FACE THROUGHOUT