Permit: T05CM03605

Parcel: 125076370

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T05CM03605

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
11/04/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*FACILITY HAS MINIMUM PLUMBING CAPABILITY IE: HANDICAPPED RESTROOMS OK
INDERECT WASTE PIPING OVER 5' TO BE DIRECTLY TRAPPED
INDERECT PIPING TO BE SUPPORTED
INDERECT WASTE TO HAVE 1" AIR GAP
CONTRACTOR REQUESTS TEMP C OF O OK SUBJECT TO OTHER INSPECTORS AND STEVE LONG
11/04/2005 PLUMBING - FINAL Approved 1) PLUMBING FINAL OK
2) OK FOR C OF O PENDING ANY OTHER INSPECTIONS
11/02/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*T.I FOR RESTAURANT INCLUDES BOILER ON ROOF AND STORAGE TANK ON GROUND FLOOR.
GAS 1" OFF OF MAIN ( REMOVE UNION) TRANSITION TO CSST AND PIPE TO BOILER
NO REDLINES ON SITE GAS DELETION AND WATER DELETION TO BE INCLUDED ON REVISION
PRESSUME TEST OK
11/01/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*THIS IS NOT A COMPLETE LIST. ROOF TOP WORK IS INCOMPLETE. CSST IS INSTALLED WITHOUT INSPECTION THIS PIPING WILL REQUIRED REVISED APPROVED PLAN WITH INSPECTION TEST.
10/20/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) LEFT GAS CARD
10/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*HOOK UP ALL GAS APPLIANCES