Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/30/2005 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Provide 6" clearance between pex and B-vent Provide anchor bolts at 16" on center per plan at shearwall Bearing walls require studs at 16" on center stair Powder room dwv out of wall No potable water test All items repeat You have 5 days to pay a reinspection fee Stopped inspection-too many items |
|
| 12/27/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) PROVIDE 4-2 X 4 POSTS UNDER GLB 2) CONNECT STAIR LEDGER TO SOMETHING 3) NO DWV WATER TEST 4) PROVIDE 6" CLEARANCE BETWEEN PEX AND B-VENT 5) PROVIDE ANCHOR BOLTS PER PLAN 6) NO POTABLE WATER TEST 7) CONDENSATES NOT CONNECTED 8) POWDER ROOM DWV OUT OF WALL 9) WATER SVC STAPLED AT POWDER ROOM 10) 15 STUDS OVER NOTCHED ON NORTH WALL 11) STOPPED INSPECTION-TOO MANY ITEMS |
|
| 12/21/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER TIM |