Inspection Status: Approved

Inspection History: STUCCO MESH

Permit Number - T05CM03581

Inspection Description - STUCCO MESH

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2006 STUCCO MESH Approved IVRS - Inspection :*
02/16/2006 STUCCO MESH Not ready for Inspection IVRS - Inspection :*
1) STILL LATHING
2) IN GARAGE NAIL SHEAR 2ND FLOOR ABOVE ?, NAIL OSB IN GARAGE STRAP 4' ON CENTER 1ST AND 2ND FLOOR
3) MECHANICAL STRAP ?
4) GAS B/B/ NOT ON PLAN 50,000 BTU-APPROX 90' USE 3/4", MX ON PLAN FOR 25,000-90' 1/2" DIAMETER
5) COMB/RELIEF DUCTS NOT INSTALLED
6) 2ND FLOOR DUCT NOT COMPLETED
7) FIRE STOP AT FURNACE FLUE CEILING 2ND FLOOR
8) OVER SPAN STUD AT H20 HTR FLUE MAX 60 DEGREE ON FLUE