Inspection History Details
Inspection Status: Approved
Inspection History: STUCCO MESH
Permit Number - T05CM03581
Inspection Description - STUCCO MESH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2006 | STUCCO MESH | Approved | IVRS - Inspection :* | |
02/16/2006 | STUCCO MESH | Not ready for Inspection | IVRS - Inspection :* 1) STILL LATHING 2) IN GARAGE NAIL SHEAR 2ND FLOOR ABOVE ?, NAIL OSB IN GARAGE STRAP 4' ON CENTER 1ST AND 2ND FLOOR 3) MECHANICAL STRAP ? 4) GAS B/B/ NOT ON PLAN 50,000 BTU-APPROX 90' USE 3/4", MX ON PLAN FOR 25,000-90' 1/2" DIAMETER 5) COMB/RELIEF DUCTS NOT INSTALLED 6) 2ND FLOOR DUCT NOT COMPLETED 7) FIRE STOP AT FURNACE FLUE CEILING 2ND FLOOR 8) OVER SPAN STUD AT H20 HTR FLUE MAX 60 DEGREE ON FLUE |