Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/01/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE CUT STUD IN KITCHEN 2) PROPERLY VENT ROOF |
|
| 10/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANCAKE AT BACK PATIO MUST BE GROUNDED 2) WIRE BOX AT BACK OF HOUSE 3) VACUUM BREAKER REQUIRED ON HOSE BIB 4) SUBMIT LIGHTING SCHEDULE FOR APPROVAL OF EXTERIOR LIGHTS 5) BLOCK STUD BAYS FOR RETURN AIR 6) TERMINATE WIRE IN CLOSET IN APPROVED OUTLET BOX 7) FILL DWV 8) EAVE VENTS NOT PER PLAN 9) INSTALL FASCIA AND BARGE RAFTERS 10) REPLACE CUT STUD AT KITCHEN HOOD VENT 11) STOPPED INSPECTION |
|
| 10/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST HAVE ATTIC ACCESS 2) BLOCK TOP AND BOTTOM COMUSTION VENTS GARAGE 3) INSTALL H20 HEATER PTR LINE TO EXTERIOR 4) WINDOWS NOT PER PLAN 5) FURNACE LOCATION NOT PER PLAN 6) INSTALL ROOF JACKS ALL PENETRATIONS 7) MUST INSTALL PLATFORM FOR H20 HEATER 8) WASHER BOX TO HIGH 9) GAS TEST TOO LOW 10) BLOCK 3 SIDES MECH VENTS CEILING 11) NO TEST DWV 12) INTERIOR WALL OMITTED BETWEEN LIVING AND DINING ROOM 13) STOPPED INSPECTION-AS BUILTS FOR APPROVAL |