Permit: T05CM03552

Parcel: 140377890

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/01/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/23/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAILS OVERSUNK IN FRONT SHEAR
2) SHEAR BLOCKS IN MASTER BEDROOM
3) FRONT COLUMN TO BE SHEARED ALL 4 SIDES PER 12B/SD3
4) DBL TOP PLATE SPLICE AT SOUTH SIDE OF ENTRY DOESN'T MEET 4' REQUIREMENT MUST STRAP
5) BLOCK OVER FRAME TRANSITION ABOVE BED 2
6) NOT MEETING HIP JACK NAILING REQUIREMENTS 2 16D NAILS
7) HIP TRUSS NOT NAILED INTO HANGER
8) MINIMUM 2 AB'S PER PLATE
9) HIP BLOCKS REQUIRED ON EAST END OF MAIN RIDGE
10) STOPPED INSPECTION