Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM03547
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
06/19/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. STILL NEED PCWM OK TO DISCHARGE. 2. PROVIDE BACKFLOW CERTS. FOR ASSEMBLIES SUPPLYING COFFEE DISPENSER. |
|
06/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. T&P RELIEF DRAINS SHALL TERMINATE TO AN APPROVED RECEPTOR NOT TO DRAIN PAN. 2. INSULATE HW RECIRC PIPING. 3. SECURE CLEAN OUT BEHIND WOMEN'S WC ON SECOND FLOOR. 4. INSTALL TRAP ADAPTOR FITTINGS AT LAVATORIES. 5. PROVIDE PCWM OK TO RELEASE 6. INSTALL VENDING EQUIPMENT WHICH CONNECTS TO WATER AND DRAIN OR PROVIDE LITERATURE AND UPC LISTING OF VENDING EQUIPMENT. IF COFFEE DISPENSER IS NOT LISTED BY UPC A BACKFLOW PREVENTER IS REQUIRED. BACKFLOW CERTS FOR ICE MAKERS RECEIVED. |
|
05/25/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL. 2. FIRST FLOOR TRIM OK WILL INSPECT FINAL, FLOOR AT A TIME |