Permit: T05CM03547

Parcel: 12810079C

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05CM03547

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
1. REDLINES SHOW ACTUAL ROUTING
2. REVISION CLARIFIES YARDWATER AND RP SIZES
3. OK TO COVER
WILL CHECK RPPBP CERTIFICATION IN FINAL
12/07/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*3" TYPE K UNDER STAIRWAY # 8 WI? RISER OK
NEED TO SEE CONNECTION TO PVC YARD WATER.
11/07/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) TWO, 2" METERS WITH 2" TO THE RPPBP'S 2 1/2" OUTLET WITH BOTH 2 1/2" TIED INTO 3" YARDWATER OK
2) PRESSURE TEST OK
3) HAVE REVISED PLAN STAMPED BY REVIEWER
4) INSTALL AVB ON TEMP HOSE BIB
5) OK TO COVER
10/11/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :* 3" PVC SCH 40 FROM 10' EAST OF METER ( WILL NEED TO SEE NEW 90 DEGREEE TO METER WITH CORRECT BACKFLOW PROTECTION) HEADS SOUTH APP. 40' THEN EAST 85' INCLUDING 3/4" TO CONST TRAILER FOR TEMP HOSE BIB. 100 PSI TEST OK. PROVIDE VACUUM BREAKER ON HOSE BIB. PROVIDE REVISED CITY APPROVED PLANOF ACTUAL INSTALLATION. NEED TO VIEW CONTINUATION INTO BUILDING & ?? STRUCTURE. COVER AT OWN RISK.
10/10/2005 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*NO FEMALE THREADED PLASTIC FITTING SHALL BE USED ON WATER PIPING
PROVIDE AIR OR WATER TEST ON PIPING
10/06/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) PLAN CONFLICT BETWEEN SITE AND PLUMBING
2) PLEASE PROVIDE INFORMATION ON THIS WITH TEST ON PIPING