Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T05CM03547
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* 1. REDLINES SHOW ACTUAL ROUTING 2. REVISION CLARIFIES YARDWATER AND RP SIZES 3. OK TO COVER WILL CHECK RPPBP CERTIFICATION IN FINAL |
|
12/07/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*3" TYPE K UNDER STAIRWAY # 8 WI? RISER OK NEED TO SEE CONNECTION TO PVC YARD WATER. |
|
11/07/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) TWO, 2" METERS WITH 2" TO THE RPPBP'S 2 1/2" OUTLET WITH BOTH 2 1/2" TIED INTO 3" YARDWATER OK 2) PRESSURE TEST OK 3) HAVE REVISED PLAN STAMPED BY REVIEWER 4) INSTALL AVB ON TEMP HOSE BIB 5) OK TO COVER |
|
10/11/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 3" PVC SCH 40 FROM 10' EAST OF METER ( WILL NEED TO SEE NEW 90 DEGREEE TO METER WITH CORRECT BACKFLOW PROTECTION) HEADS SOUTH APP. 40' THEN EAST 85' INCLUDING 3/4" TO CONST TRAILER FOR TEMP HOSE BIB. 100 PSI TEST OK. PROVIDE VACUUM BREAKER ON HOSE BIB. PROVIDE REVISED CITY APPROVED PLANOF ACTUAL INSTALLATION. NEED TO VIEW CONTINUATION INTO BUILDING & ?? STRUCTURE. COVER AT OWN RISK. | |
10/10/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*NO FEMALE THREADED PLASTIC FITTING SHALL BE USED ON WATER PIPING PROVIDE AIR OR WATER TEST ON PIPING |
|
10/06/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) PLAN CONFLICT BETWEEN SITE AND PLUMBING 2) PLEASE PROVIDE INFORMATION ON THIS WITH TEST ON PIPING |