Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 04/06/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* SOFFIT @ ROOM #1015 ENTIRE 4TH FLOOR (EXCLUDING ELEVATOR AREA) |
|
| 03/28/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* EXTERIOR SHEATHING WEST SIDE OF BUILDING, SOUTH OF STAIRWAY. |
|
| 03/21/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 3RD FLOOR DONE |
|
| 03/03/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 2ND FLOOR COMPLETE |
|
| 02/24/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :*1ST FLOOR OK EXCEPT FIRE STOP @ 1 LOCATION IN CLOSET UNDER STAIR AND 8 PENETRATIONS @ ELECTRIC ROOM | |
| 02/16/2006 | SHEET ROCK NAILING | Not ready for Inspection | IVRS - Inspection :* NO SPECIFIC AREA COMPLETE |
|
| 02/15/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* | |
| 02/09/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR ABOVE CEILING AND EXTERIOR WALLS OK TO TAPE |
|
| 02/06/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* ELEV & ELEC ROOMS ARE 2 HR RATED - YOU MUST HAVE FIRE STOP IN PLACE @ PENETRATIONS |
|
| 01/25/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* OK TO TAPE ROCK ABOVE CEILING EXCEPT AROUND PENETRATIONS. |