Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T05CM03547
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | BUILDING PRE-SLAB | Approved | IVRS - Inspection :* | |
01/06/2006 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :*STAIRS AND LANDING SOUTH STAIR WELL OK 4TH FLOOR SLAB OK TO PLACE CONCRETE A) PROVIDE SPECIAL INSP REPORTS FOR DECK WELDING B) SHEAR COLLECTORS MISSING PER KEYNOTE 7 |
|
12/27/2005 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :*3RD FLOOR SUPER STRUCTURE OK. I STILLNEED SPECIAL INSP REPORTS P. FOR H.S BOLTS AND WELDS. CONTRANCTOR HAS SUBSTITUTED A 12" ON STUGGER ( 6" O.C ON LINE) STUD PATTERN ON BY BEANS RATHER THAN TANDEM PATERN REQUIRED BY DETAIL. T24. CONTRACTOR TO PROVIDE RFI FROM ENGINEER FOR THIS STANDARD FIX. OK TO PLACE 3RD FLOOR SLAB |
|
12/21/2005 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :*2ND FLOOR FECK APPROVED. ALL WELDS, STUDS AND SPECIAL INSP. REVIEWED OK TO PLACE CONCRETE |
|
12/09/2005 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR |