Permit: T05CM03547

Parcel: 12810079C

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Permit Number - T05CM03547

Inspection Description - BUILDING PRE-SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2006 BUILDING PRE-SLAB Approved IVRS - Inspection :*
01/06/2006 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*STAIRS AND LANDING SOUTH STAIR WELL OK
4TH FLOOR SLAB OK TO PLACE CONCRETE
A) PROVIDE SPECIAL INSP REPORTS FOR DECK WELDING
B) SHEAR COLLECTORS MISSING PER KEYNOTE 7
12/27/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*3RD FLOOR SUPER STRUCTURE OK. I STILLNEED SPECIAL INSP REPORTS P. FOR H.S BOLTS AND WELDS.
CONTRANCTOR HAS SUBSTITUTED A 12" ON STUGGER ( 6" O.C ON LINE) STUD PATTERN ON BY BEANS RATHER THAN TANDEM PATERN REQUIRED BY DETAIL. T24. CONTRACTOR TO PROVIDE RFI FROM ENGINEER FOR THIS STANDARD FIX. OK TO PLACE 3RD FLOOR SLAB
12/21/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*2ND FLOOR FECK APPROVED. ALL WELDS, STUDS AND SPECIAL INSP. REVIEWED
OK TO PLACE CONCRETE
12/09/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
1) 1ST FLOOR