Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T05CM03547
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
05/12/2006 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* LIGHT POLE BASES OK |
|
11/04/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*COLUMN FOOTING @ LINES Z/1.5 | |
11/01/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*FI FOOTING LINE 2/B,C,D AND LINE 3/D, F 15 FOOTING 205/D OK | |
10/24/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*I-D FOOTING DROPPED TO 3'6" BELOW FF PER RFI 30 | |
10/17/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*STAIR FOOTING LINE O OK | |
10/13/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*LINE A/F3 FOOTINGS @ 1,2,3. BOND MADE TO STEEL ANCHOR BELTS WITH 3/0 AWG COPPER -20' IN FOOTING AND BONDING CLAMPS OK | |
10/04/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*GRID LINE 4 AND E FTG F2 F3 OK | |
10/03/2005 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*ELEVATOR PIT & STAIRWAY B OK |