Permit: T05CM03540

Parcel: 141018390


Addresses:

6059 S CEDAR ELM LN


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM03540

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2006 BUILDING - FINAL Approved IVRS - Inspection :*
03/10/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONE P.T. CABLE NOT PULLED, AT SERVICE PANEL
2) PLUG HOLE IN SERVICE PANEL
3) NEED HOUSE ADDRESS
4) GFCI IN 1ST FLOOR BATH WON'T RESET
5) TRIM OUT 3" CLEANOUT IN GARAGE
6) ARC FAULT IN 2 BEDROOMS 2ND FLOOR WON'T TRIP
7) INSTALL 20/20 FUSES IN FURNACE DISCONNECT
8) LABEL IN SERVICE PANEL FURNACE, TWO A/C'S LABELED
9) NEED BUSHING IN LIGHT CAN ATTIC