Permit: T05CM03484

Parcel: 13219015B


Addresses:

2220 E BENSON HY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM03484

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
05/12/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AN AVB IS NOT TO HAVE ANY VALVES DOWNSTREAM. THE CORRECT DEVICE FOR BACKFLOW PROTECTION IS A PVB.
A PVB DOES REQUIRE CERTIFICATION.
2. INTERMIXING OF DISSIMILAR METALS IS NOT ACCEPTABLE IN NEW CONSTRUCTION.