Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AN AVB IS NOT TO HAVE ANY VALVES DOWNSTREAM. THE CORRECT DEVICE FOR BACKFLOW PROTECTION IS A PVB. A PVB DOES REQUIRE CERTIFICATION. 2. INTERMIXING OF DISSIMILAR METALS IS NOT ACCEPTABLE IN NEW CONSTRUCTION. |