Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T05CM03442
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2005 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
08/16/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STEEL ON GROUND 2) CLEAN FOOTERS 3) HOLDOWNS TO CLOSE TO FORMS, CHECK CATALOG FOR CLEARANCE 4) HOLDOWNS TO CLOSE TO DIRT 5) NEED 3" CLEARANCE FOR STEEL THRU-OUT 6) PLUMBING EXPOSED |
|
08/15/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL DEPRESSED SLAB AREA AT N.E. CORNER WITH STEEL PER KEYNOTE #7 2) EAST SET BACK OK. SOUTH SETBACK SHOWS 10'-3" AS APPOSED TO SITE PLANS 8'-6" 3) GARAGE DOOR FOOTING FULL OF WATER-CHECK STEEL 4) UFER CLAMPS ON WRONG WAY FOR #4'S |