Permit: T05CM03385

Parcel: 111083730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03385

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/13/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) A BOX IS NEEDED FOR LIGHT FIXTURE
2) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8
3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR TO BE FLUSH IN COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20
4) FILL UNUSED OPENING IN JUNCTION BOX-EXPOSED CONDUCTORS TO COMBUSTIBLES-DINING LIGHT
5) A DISCONNECTING MEANS IS NEEDED FOR A/C UNITS. ALSO USE APPROVED METHOD TO PROTECT CONDUCTORS
6) CHECK PLENIUM RATING OF WIRING METHODS 310.22 AND 300.22