Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03385
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/13/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) A BOX IS NEEDED FOR LIGHT FIXTURE 2) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8 3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR TO BE FLUSH IN COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20 4) FILL UNUSED OPENING IN JUNCTION BOX-EXPOSED CONDUCTORS TO COMBUSTIBLES-DINING LIGHT 5) A DISCONNECTING MEANS IS NEEDED FOR A/C UNITS. ALSO USE APPROVED METHOD TO PROTECT CONDUCTORS 6) CHECK PLENIUM RATING OF WIRING METHODS 310.22 AND 300.22 |