Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOF 1. MAINTENANCE OUTLETS TO BE PER 210.63 2. FINISH PREVIOUS ITEMS |
|
| 10/02/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EMERGENCY NOT WORKING (LIGHTING) 2. WHERE IS CONTACTOR AND ASSOCIATED WIRING AS PER PLANS. 3. PLEASE PROVIDE A LETTER FOR DELETION OF WALL & RECEPTACLES. ROOF: 1. SUPPORT RACEWAYS INSIDE UNITS 2. BOND RACEWAYS 3. GFCI'S NO POWER 4. MAINTAIN WORKING CLEARANCES OF A/C DISCONNECT 5. SUPPORT PHONE CABLES UP OFF ROOF (800.6) |