Permit: T05CM03374

Parcel: 13322500E


Addresses:

7125 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/11/2006 ELECTRIC - SERVICE UPGRADE Approved
08/30/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
08/28/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT M/C CABLE WITHIN 12" OF BOXES
2. SUPPORT VDV CABLING 725.6 & 800.6 NOT OFF OF OR OVER PIPES
3. CONDUIT NOT MORE THAN 360 DEG. IN RUN
4. SECURE ALL FIXTURES TO GRID
5. A BOND WILL BE NEEDED FOR POWER