Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2006 | ELECTRIC - ABOVE CEILING | Approved | OK TO TILE | |
| 08/30/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. FINISH SUPPORTING VDV CABLEING - 725.6 2. PLEASE PROVIDE LISTING PAPERWORK FOR PIN ADAPTORS. 3. BOND FLEX RACEWAYS AT TRANSFORMER 4. CANNOT STACK LUGS 5. DERATE CONDUCTORS PER 310.15 6. BONDING JUMPER TO BE AS PER 250.102 & 250.66 7. PROVIDE NEUTRAL KIT PER MANUFACTURER 110.3 8. PREVENT OBJECTIONABLE CURRENT 250.6 9. NEED REJECTION PIN PARTS FOR DISCONNECTS |
|
| 08/28/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |