Permit: T05CM03374

Parcel: 13322500E


Addresses:

7125 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/04/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/30/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT M/C CABLE WITHIN 12" OF BOXES AT CANS AND IN WALLS.
2. JUNCTION BOXES TO ACCESSIBLE AFTER HARD LID.
3. WHAT IS OULET ON OUTSIDE OF FIRE RISER ROOM.
NOT ON PLANS.
03/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS OUTSIDE SOFFITS (2)
1. PLEASE PROVIDE ACCESS AS PER 600.21
2. WHERE IS SIGN CIRCUIT AS PER 600.5
3. PLEASE PROVIDE LIGHTING AS PER 210.70 (C)