Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM03365

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2006 FRAMING Approved IVRS - Inspection :*
01/11/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED 2" VENT AT 2ND FLOOR TOILET
2) ROMEX NOT CONNECTED ENTRY LIGHT, ROLLED UP ROMEX FIT LID
3) RECEPTACLE NOT WIRED LIVING ROOM
4) WRONG SIZE HANGER
5) NEED HUS 410 HANGER AT ROOF GIRDER
6) LARGE GIRDER IS 3 PT BEARING, ADD DBL 2 X DOWN TO FLOOR
7) BLOCK FLOOR OSB AT JOINT WEST BEDROOM
8) BATHROOM ABOVE KITCHEN NOT PLUMBED CORRECTLY
9) FURNACE FLUE NOT SNAPPED TOGETHER AT JOINT 2ND FLOOR CLOSET, CEILING
10) NEED H20 POTABLE TEST
11) MISSING BANG PLATES THRU-OUT SEE GARAGE SIDE OF T3P CONDENSATE
12) NEED DWV TEST
13) POSITIVE PITCH LAUNDRY VENT
14) SECURE SWITCH 2ND FLOOR BATH
15) LOWER FIRE STOP GARAGE DROP