Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM03364
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
12/27/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) FILL ALL HOLES IN GIRDER HANGER WITH SINKERS 4,691 POUNDS AT GIRDER Q10 INTERIOR BEARING ADD DBL STUDS UNDER PROPERTY LINE 2) NEED RAT RUNS ON Q5, Q8, R2 TRUSSES 3) OK TO DRY IN ROOF AND WALLS |
|
12/19/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) M-3 TRUSS 1609 AT HANGER, FILL ALL HOLES WITH 16 COMMON HVS 410=2509 16S 2) BLOCK AND NAIL AT HIP REAR, OSB TURNED PARALELL TO TRUSSES 3) INSTALL RAT RUNS 4) TRUSS DRAWINGS MISSING Q10 2 PLY GIRDER, DRAWINGS SHOW Q9 AS DBL GIRDER |
|
12/14/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING NAILING ON ROOF MARKED IN BLACK 2) HANGER AT M-3 GIRDER TO GIRDER 3) NEED TRUSS DRAWINGS TO REFLECT ROOF ABOVE CLEAR STORY 4) STOPPED INSPECTION |