Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM03358
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) CHECK HEIGHT OF DIRECT VENT CHIMNEY |
|
04/21/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) SEE LAST INSPECTION |
|
04/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) 1ST/2ND FLOOR STRAPS 48" ON CENTER 2) FRONT DOOR TRIMMER 1/2" PLY 3) NAIL AND OR BLOCK HORIZONTAL JOINTS EXT. SHEAR 4) BRING ALL BEARING PT. LOADS DOWN TO CONC SLAB 5) SHIM 3PT BEARING TRUSSES 6) 10/DT1 BEAM HANGER PLAN CALLS FOR HUS 410 SIMPSON ADVANCED INSTALLED CHECK EQUAL 7) NAIL DOWN ALL EXT. & SHEAR WALL PLATES PER PLAN 8) INSTALL MSTC STRAPS 2ND FLOOR A TOTAL 9) TWO GIRDER TRUSSES ROOF ARE NOT 3 PT BEARING NOTCH UNDER DBL STUD AT PALTES FOR DEFLECTION |