Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM03347
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) NEED TRUSS DRAWING FOR ?6G1 TRUSS TOTAL OF TWO OF THEM IN 1356 C-1 UPPER SET OF TRUSSES 2) FT2 TRUSS NOT BUILT PER DRAWING |
|
11/02/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PULL P.T. CABLES 2) WRONG SIZE NAILS IN GIRDER TO TRUSS HANGER 3) NEED CORRECTED TRUSS DRAWINGS 4) SHEAR NEEDS TO BE STRAPPED TO TRUSS TOP CHORD 5) NAIL LARGE SHEAR PANELED BOXES AT 4" ON CENTER 6) NEED CRIPPLE AT 2ND FLOOR 3PT BEARING 7) CHECK ALL NAIL SIZES IN THA TYPE HANGER AT STAIR BEAM TO BEAM 8) TIE COLUMN TOGETHER AT FRONT |