Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/08/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REAR WALL NOT BEARING ON RIM JOIST 2) REMOVE RIBBON-SEE ITEM 3 OF 11/04/05 INSPECTION |
|
| 11/04/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GABLE END TRUSSES NOT CLIPPED ON END PER 1/SD3 2) S.W. CORNER NOT CLIPPED AT SILL PLATE 3) SECOND FLOOR SILL PLATE NOT BEARING ON STRUCTURE AT N.W. CORNER-REMOVE RIBBON ON WEST WALL FOR SILL PLATE INSPECTION 4) RIBBON OSB NORTH WALL NOT NAILED PER 1/SD2 5) NORTH P-1 NOT PER PLAN 6) OSB ROOF PANELS MUST SPAN 3 TRUSSES OR TWO BAYS 7) ENTRY COLUMNS REQUIRE TWO ANCHOR BOLTS PER SILL PLATE |