Permit: T05CM03317

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/04/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PROVIDE LETTER TO BUILDING
INSPECTOR CONCERNING EMERGENCY LIGHTING ALSO, SHELL FINAL HAS NOT YET BEEN APPROVED.
07/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STRAP MC WITHIN 12" OF BOX ENTRY.
2. CORRECTLY IDENTIFY PANEL DIRECTORY.
3. EMERGENCY LIGHTING NOT WORKING PER PLAN.
4. STRAP H.W.T FLEX
5. CORRECTLY IDENTIFY RTU DISCONNECT