Permit: T05CM03317

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/04/2006 ELECTRIC - INTERMEDIATE Approved
06/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WATER HEATER ROOM WALLS
06/21/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MC NEEDS TO BE SECURED WITHIN 12" OF TERMINATION.
2. TRACK LIGHTING NEEDS SUPPORT EVERY 4'
3. COVER OPEN HOLES IN J-BOXES AND INSTALL MISSING COVERS.
4. MAKE SURE J-BOX FOR WATER HEATER WILL BE ACCESSIBLE