Permit: T05CM03315

Parcel: 106120540

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/25/2007 ELECTRIC - INTERMEDIATE Approved
10/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROPERLY GROUND ALL METAL BOXES.
2. IN BEDROOMS -- NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINES.
3. ALL 3 WIRE HOME RUNS NEED NEUTRALS PIG TAILED.
4. NEED BUSHING FOR CONDUCTORS ENTERING PANEL.

OK ELECTRICAL COVER
AFTER CORRECTIONS MADE.