Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* NOTE: DO A BETTER JOB OF SECURING/SUPPORTING LOW VOLTAGE WIRING NEC 800.6 |
|
| 04/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY NEUTRALS (WHITE) USED AS HOT NEC 310 2. GROUND ALL METAL BOXES NEC 250 3. NEED HALL OUTLETS NEC 210.52 (H) 4. FINISH LOW VOLTAGE WIRING NEC 800.6 OK TO INSULATE ONLY |
|
| 04/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CALL FOR INSPECTION WHEN WORK IS COMPLETE. |